parallel, enter average installed PV power for each PV
input, as shown in the examples.

PV String Configuration

Enter this value for

“Installed PV power”

Example 1: PV1, PV2 and PV3 are each set

to individual mode.

Nominal PV power installed:

PV 1: 6000 W

PV 1: 6000 W

PV 2: 6000 W

PV 2: 6000 W

PV 3: 3000 W

PV 3: 3000 W

Example 2: PV1 and PV2 are set to

parallel mode and have a total of 10 kW

PV power installed. PV3 is set to

individual mode and has nominal 4 kW

PV power.

PV 1: 5000 W

PV 2: 5000 W

PV 3: 4000 W

Example 3: PV1 and PV2 are set to

parallel mode and have a total of 11 kW

PV power installed. PV3 is set to [Off] and

has no PV installed.

PV 1: 5500 W

PV 2: 5500 W

PV 3: 0 W

Table 3.2 Examples of Installed PV Power

The display will now show ‘Select country’. The setting is
‘undefined’ at initial start-up. Press [

▼] to scroll down

through the list of settings. To select the desired setting,
press [OK].

Illustration 3.7 Select Country

Illustration 3.8 Select Grid Code

The display will now show ‘Select grid code’. The grid code
is set to ‘undefined’ at initial start-up. To select the grid

code, press [OK]. Press [

] to scroll down through the list.

Select the grid code for the installation by pressing [OK]. It
is very important to choose the correct grid code.

Illustration 3.9 Confirm Grid Code Selection

To confirm, select the grid code again and press [OK]. The
settings for the chosen grid code have now been
activated.

WARNING

Correct selection of grid code is essential to comply with
local and national standards.

Initial Setup and Start

22

L00410568-03_2q / Rev. date: 2014-06-20