ID

Status
message

Description

Action

DNO Hotline PV

34–37

Residual Current Monitoring Unit

(RCMU) has measured an

excessive current.

Turn both DC and AC off and wait until the display turns

off. Then turn on DC and AC and observe if the event

reoccurs. If the event reoccurs, call the installer.

Installer: Visual inspection of all PV cables and modules.

-

x

-

40

AC grid not

OK

The AC grid has been out of

range for more than 10 minutes

(frequency and/or voltage).

Call the installer and inform about Frequency, SW version

and Grid code setting

Installer: Check the AC installation.

x

-

-

41–43

The inverter has detected that

grid voltage was below a certain

level.

If this event is reported several times each day, contact the

installer.

Installer: Perform on-site grid analysis.

47

PLA below

threshold

The inverter disconnects from

grid if PLA is below 3% of

nominal power.

Contact the DNO and obtain status on active power

reduction (PLA).

x

-

-

48–53 Grid

frequency

too low or

too high

Call the installer and inform about the grid frequency.

Check the AC installation.

x

-

-

54–56

DC grid current too high (stage

2).

For occurrence several times daily, contact installer.

Installer: Perform on-site grid analysis.

x

-

-

246

A grid event was detected and

inverter was stopped by the

redundant safety circuit.

A grid event was detected and inverter was stopped by the

redundant safety circuit. Check the event log. If the majority

of entries are of type 246, call the service department.

Otherwise wait 24 hours and check again.

-

x

-

Table 4.2 Grid-related Events

PV-related Events

ID

Status
message

Description

Action

DNO Hotline PV

100-102

PV negative

Input current is negative, polarity

incorrect.

Call the installer.

Installer: Check polarity, if correct, call service.

-

-

x

103-105

PV current is

too high/

waiting.

Too many PV modules connected in

parallel. Should only appear on newly

installed systems.

Call the installer.

Installer: Check no. of strings in parallel and

current ratings. Has the current limit been

exceeded? Has the inverter derated on PV

current? Reconnect strings in parallel, possibly

install a second inverter.

-

x

x

112-114

PV config fault

Call the installer.

Installer: Call service.

-

-

x

115

PV ISO too low

The resistance between ground and

PV is too low for the inverter to start

up. This will force the inverter to make

a new measurement after 10 minutes

have passed.

Make a visual inspection of all PV cables and

modules for correct installation according to

the installation guide. The event could indicate

that the PE connection is missing.

-

x

x

116-118

PV wrong polarity

Call the installer.

Installer: Call service.

-

x

x

121-123,

125

PV ISO low PV1, PV2, PV3, multiple

(related to 115)

Call the installer.

Installer: Call service.

-

x

x

258

PV voltage too

high/waiting

PV voltage is too high.

Check that installation and layout correspond

to recommendations in the manuals.

-

x

x

Table 4.3 PV-related Events