Illustration 5.12 Overview of Inverter with Torque Indications

2

Parameter

Tool

Tightening Torque

1

M32 cable gland

body

Wrench 42 mm

7.5 Nm

2

M32 cable gland,

compression nut

Wrench 42 mm

5.0 Nm

3

Terminals on AC

terminal block

Pozidriv PZ2 or

Straight slot 1.0 x

5.5 mm

2.0 - 4.0 Nm

4

PE

Torx TX 20 or

Straight slot 1.0 x

5.5 mm

2.2 Nm

Table 5.12 Nm Specifications 2

5.7 Mains Circuit Specifications

FLX series

5

6

7

8

9

10

12.5

15

17

Maximum inverter current, I

acmax

7.5 A

9 A

10.6 A

12.1 A

13.6 A

15.1 A

18.8 A

22.6 A

25.6 A

Recommended blow fuse type gL/gG

*)

10 A

13 A

13 A

13 A

16 A

16 A

20 A

25 A

32 A

Recommended automatic fuse type B or C

*)

16 A

16 A

16 A

20 A

20 A

20 A

25 A

25 A

32 A

Table 5.13 Mains Circuit Specifications

*)

Always choose fuses according to national regulations.

5.8 Auxiliary

Interface

Specifications

Interface

Parameter

Parameter Details

Specification

RS-485 and Ethernet

Cable

Cable jacket diameter (

⌀)

2x5-7 mm

Cable type

Shielded Twisted Pair (STP CAT 5e or

SFTP CAT 5e)

2)

Cable characteristic impedance

100

Ω – 120 Ω

RJ-45 connectors:

2pcs RJ-45 for RS-485

2pcs RJ-45 for Ethernet

Wire gauge

24-26 AWG (depending on mating

metallic RJ-45 plug)

Cable shield termination

Via metallic RJ-45 plug

Galvanic interface insulation

Yes, 500 Vrms

Direct contact protection

Double/Reinforced insulation

Yes

Short-circuit protection

Yes

RS-485 only

Cable

Max. cable length

1000 m

Max. number of inverter

nodes

63

Ethernet only

Communication

Network topology

Star and daisy chain

Cable

Max. cable length between

inverters

100 m

Max. number of inverters

100

1)

Table 5.14 Auxiliary Interface Specifications

1)

Max. number of inverters are 100. If GSM modem is used for portal

upload, the number of inverters in a network is limited to 50.

2)

For outdoor use, we recommend outdoor burial type cable (if

buried in the ground) for both Ethernet and RS-485.

Technical Data

46

L00410568-03_2q / Rev. date: 2014-06-20

5