5.5 Cable

Specifications

NOTICE

Avoid power loss in cables greater than 1% of the
nominal inverter rating by following the values stated in
the tables and illustrations.

NOTICE

Table states only cable lengths less than 100 m.

Specification

FLX series

AC cable maximum

length [m]

AC cable size

5

6

7

8

9

10

12.5

15

17

2.5 mm

2

43 m

36 m

31 m

27 m

24 m

21 m

1)

1)

1)

4 mm

2

69 m

57 m

49 m

43 m

38 m

34 m

27 m

2)

2)

6 mm

2

86 m

74 m

64 m

57 m

52 m

41 m

34 m

30 m

10 mm

2

95 m

86 m

69 m

57 m

51 m

16 mm

2

92 m

81 m

AC cable type

5-wire copper cable

AC cable outer diameter

18-25 mm

AC cable insulation strip

Strip 16 mm length of insulation from all 5 wires

PE cable diameter

Equal to or greater than diameter of AC phase cables

Table 5.9 AC Cable Specifications

1)

Using cable with a diameter less than 4 mm

2

is not recommended.

2)

Using cable with a diameter less than 6 mm

2

is not recommended.

Specification

FLX series

DC cable type

Min. 1000 V, 13.5 A

DC cable length

DC cable size 4 mm

2

- 4.8

Ω /km

< 200 m*

DC cable size 6 mm

2

- 3.4

Ω /km

200-300 m*

Mating connector

Sunclix PV-CM-S 2,5-6(+) / PV-CM-S 2,5-6(-)

Table 5.10 DC Cable Specifications

* The distance between inverter and PV array and back, plus the

cumulative length of the cables used for PV array installation.

Consider also the following when choosing cable type and
cross-sectional area:

Ambient temperature

Layout type (inside wall, under ground, free air
etc.)

UV resistance