Illustration 2.15 Installation Area

Illustration 2.16 AC Cable Wire Strip

On the AC cable, strip insulation on all 5 wires. The PE wire
must be longer than the mains and neutral wires. See
Illustration 2.16.

Illustration 2.17 AC Connection Area

L1, L2, L3

3 mains wires

N

Neutral wire

PE1

Primary protective earth

PE2

Secondary protective earth

1.

Verify that the inverter rating matches the grid.

2.

Ensure that main circuit breaker is released, and
take precautions to prevent reconnection.

3.

Open the front cover.

4.

Insert the cable through the AC gland to the
terminal blocks.

5.

Connect the 3 mains wires (L1, L2, L3), the
neutral wire (N) and the protective earth wire (PE)
to the terminal block with the respective
markings.

6.

Optional: Make an extra PE connection at the
secondary PE earthing points.

7.

All wires must be properly fastened with the
correct torque. See 5.6 Torque Specifications.

CAUTION

Check that all wiring is correct. Connecting a phase wire
to the neutral terminal may permanently damage the
inverter.

NOTICE

Tighten all screws and glands thoroughly.