Item

Unit

View

Description

Plant and

Group

Inverter

Overall plant status

-

x

Red: Plant PR <50%, or:

Any inverter in the network

- in fail safe mode, or

- missing from the scan list, no contact with the master

Yellow: Any inverter in the network

- with PR <70%, or

- in Connecting or Off grid mode

Green: Plant PR ≥70%, and

- all inverters with PR ≥70%, and

- all inverters in On grid mode

x

Red: Inverter PR <50%, or inverter has an error

Yellow: Inverter PR between 51% and 70%, or inverter in Connecting

mode

Green: No errors, and

- inverter PR ≥70%, and

- inverter in On grid mode

Current production

kW

x

x

Real time energy production level

Yield today

kWh

x

x

Cumulative yield for the day

Total revenue

Euro

x

x

Cumulative revenue earned since initial startup

Total CO

2

saving

kg

x

x

Cumulative CO

2

saved since initial startup

Performance ratio

%

x

x

Real time performance ratio

Total yield

kWh

x

x

Cumulative yield since initial startup

Power limit adjustment

%

x

Maximum power limit as % of nominal inverter AC output rating

Table 3.3 Information Displayed in Plant View, Overview Screen

NOTICE

To calculate performance ratio PR, an irradiation sensor
is required, see [Setup

Calibration].

3.3.6 Autotest Procedure

For certain grid codes, an automatic test of the inverter
can be initialised by activating the inverter autotest
procedure:

Via the web interface, go to [Inverter level: Setup
→ Setup details → Autotest] and click on [Start →
Test].

Initial Setup and Start

32

L00410568-03_2q / Rev. date: 2014-06-20

3