Supported Devices

MIBs Used

46

Alarm name

Type

MIB point

Further details

--- Converter alarms

1

---

cvalr

MIB point gives Local oscillator alarm and Power supply alarm.

mute

and

pol

are text alarms that only provide information

acvstat

MIB point gives informations for Redundancy Chain status alarms and serial link status

converter alarm.

Local Oscillator Alarm Status/health

cvalr

Local Oscillator Alarm

2

This alarm may occur if the specified converter is
not installed. It also may happen if the converter
cannot be selected with an SNMP set.

Power Supply Alarm

Status/health

cvalr

Power Supply Alarm

2

This alarm may occur if the specified converter is
not installed. It also may occur if the converter
cannot be selected with an SNMP set.

Mute

Text/health

mute

Mute converter output for the converter selected
by the most recent

cvsel

setting.

3

Polarization

Text/health

pol

Polarization setting for the converter selected by
the most recent

cvsel

setting.

3

Allowable settings:

• 0 - N/A

• 1 - None

• 2 - Horizontal

• 3 - Vertical

Serial Link Status
converter

 StatusText/health

 

acvstat

Converter serial link status indicator

• 0 = No Fault - NSU-Converter Serial Link

enabled and communicating

• 1 = Fault - NSU-Converter Serial Link enabled

and not communicating

• 2 = No Fault - NSU-Converter Serial Link

disabled

• - = No Fault - Chain position inactive

Redundancy chain
status

 StatusText/health

 

acvstat

Redundancy chain status indicator

• 0 = No Fault - chain position active

• 1 = Fault -chain position active (Fault reported

normally)

• 2 = Fault - chain position active both contacts

open

• 3 = Fault - chain position active both contacts

closed

• - = chain position inactive disconnected from

redundancy chain

• + = chain position inactive connected to

redundancy chain