96
•
An NEPS3500-A AC power frame can function properly only after you install one or two
NEPS1800-A AC power modules to it.
Table 38 Electrical parameters of power system
Model Description
Rated input
voltage range
Max input
voltage range
Max input
current
Max output power
NEPS3500-
A
3500 W AC
power frame
100 VAC to 240
VAC @ 50 Hz or
60 Hz
90 VAC to 264
VAC @ 50 Hz
or 60 Hz
16 × 2 A
3500 W (when
installed with two
AC power modules)
NEPS1800-
A
1800 W AC
power
module
100 VAC to 240
VAC @ 50 Hz or
60 Hz
90 VAC to 264
VAC @ 50 Hz
or 60 Hz
•
16 A @ 110
V
•
12 A @ 220
V
•
1200 W @ 100
VAC to 120 VAC
•
1800 W @ 200
VAC to 240 VAC
NEPS2000-
A
2000 W AC
power
module
100 VAC to 240
VAC @ 50 Hz or
60 Hz
90 VAC to 264
VAC @ 50 Hz
or 60 Hz
16 A
2000 W
NEPS800-A
800 W AC
power
module
100 VAC to 240
VAC @ 50 Hz or
60 Hz
90 VAC to 264
VAC @ 50 Hz
or 60 Hz
12 A @ 100 V 800 W
NEPS1300-
D
1300 W DC
power
module
–36 VDC to –72
VDC
–72 VDC to
–38.4 VDC
46 A @ –48 V 1300 W
NEPS2000-
D
2000 W DC
power
module
–36 VDC to –75
VDC
–72 VDC to
–40 VDC
45 A @ –48 V 2000 W
NEPS3500-
D
3500 W DC
power
module
–36 VDC to –75
VDC
–72 VDC to
–40 VDC
80 A @ –48 V 3500 W
Table 39 16 A AC power cords used in different countries or regions
1
Connector
type
Code (Length)
Countries or regions
where the type of
power cords conforms
to local safety
regulations and can be
used legally
Other countries or
regions using this type of
power cords
Countries or
regions seldom
using this type of
power cords
I type
04043396 (3
m/9.8 ft)
Mainland China
Connector outline
Power cable outline
Connector outline