beautypg.com

7 sm-ethercat error codes, 7 sm-ethercat, Error – Emerson SM-ETHERCAT 0471-0128-02 User Manual

Page 60: Codes

background image

60

SM-EtherCAT User Guide

www.controltechniques.com

Issue Number: 2

9.7

SM-EtherCAT error codes

If an error is detected during operation the module will force a trip on the drive and
update the error code parameter (Pr MM.50). Table 9.13 shows the SM-EtherCAT error

codes.

Table 9.12 SM-EtherCAT error codes

SM-EtherCAT error codes

Pr MM.50

Default

N/A

Range

0 to 255

Access

RO

Table 9.13 SM-EtherCAT error codes

Error code

Fault

1

No fieldbus mode has been selected.

2

Critical task over-run.

3

Invalid feedback source

4

Unknown drive type

5

Unsupported drive type

10

Invalid or missing application

62

Database initialisation error.

63

File system initialisation error.

64

Error initialising fieldbus stack.

74

The option module has overheated.

75

The drive is not responding.

76

The Modbus connection has timed out.

80

Inter-option communication failure.

81

Inter-option communication to slot 1 timeout.

82

Inter-option communication to slot 2 timeout.

83

Inter-option communication to slot 3 timeout.

84

Memory allocation error.

85

File system error.

86

Configuration file error.

98

The option module background task has not been

completed.

99

Software fault.