7.5.2

0x6043 vl_velocity_demand

This read only object provides the instantaneous velocity demand generated by the
drive ramp function. The value is given in rpm if the vl_dimension_factor and the
vl_setpoint_factor have the value 1, otherwise the value is in user units. Positive values
indicate forward direction and negative values indicate reverse direction.

7.5.3

0x6044 vl_velocity_actual_value

This read only object provides the velocity at the motor spindle or load. In a closed loop
system this is determined from the motor feedback device and in an open loop system it
is a copy of vl_velocity_demand.

The value is given in rpm if the vl_dimension_factor has the value of 1, otherwise the
value is in user units. Positive values indicate forward direction and negative values
indicate reverse direction.

7.5.4

0x6046 vl_velocity_min_max_amount

This object is used to configure the minimum and maximum velocity.
The value is given in rpm if the vl_dimension_factor has the value of 1, otherwise the
value is in user units.

Table 7.38 vl_velocity_demand

0x6043

vl_velocity_demand

Access: RO

Range: -32768 to +32767

Size: Signed 16

Unit: rpm

Default:

0

Description:

Provides the instantaneous velocity demand generated by the drive ramp function

Table 7.39 vl_velocity_actual_value

0x6044

vl_velocity_actual_value

Access: RO

Range: -32768 to +32767

Size: Signed 16

Unit: N/A

Default:

0

Description:

Provides the velocity at the motor spindle or load.
Only available when in vl_velocity_mode.

Table 7.40 vl_velocity_min_max_amount

0x6046

vl_velocity_min_max_amount

Sub-index 0

Access: RO

Range: N/A

Size: Unsigned 8

Unit: N/A

Default:

2

Description:

The number of last sub-indexes in this object.

Sub-index 1

Access: RW

Range: 0 to 0xFFFFFFFF

Size: Unsigned 32

Unit: rpm

Default:

0

Description:

Used to configure the minimum velocity (both in the forward and reverse direction) that the
system can operate at. Writing to this sub index will overwrite vl_velocity_min positive and
vl_velocity_min negative.

Sub-index 2

Access: RW

Range: 0 to 0xFFFFFFFF

Size: Unsigned 32

Unit: rpm

Default:

2147483647

Description:

Used to configure the maximum velocity (both in the forward and reverse direction) that the
system can operate at. Writing to this sub index will overwrite vl_velocity_max positive and
vl_velocity_max negative.