Nalog, Utput, Etup – Super Systems 9130 Series User Manual
Page 74

Series 9130 Operations Manual Rev -
73
Use Input Correction Curve
This option will allow the user to use a correction curve on the input. The options are No or Yes.
Analog Output Setup
The 9130 controller has the option of
two analog outputs. The outputs are
ranged for a 4 – 20 milliamp signal or
a 0 – 20 milliamp signal. Each output
comes with a factory default
configuration dependent on the
application. Each output can be
modified prior to shipment to your
facility or in the field by a supervisor.
Analog Output Terminals
Analog output 1 – terminals 24 and 25
Analog output 2 – terminals 25 and 26
Assignment
The analog output assignment can be modified depending on your system requirements. To change the
Assignment first select which analog output you want to change by selecting it in the pull-down menu just
below the main menu list. Clicking on this value will display an input box, and then you can use the pull-
down menu to select the desired parameter. Once selected, click OK
and the displayed assignment under
Value will be the current assignment type. The following is a list of the options:
PV 1 retrans
Input 1 retrans
Loop 1 inc
Input 2 retrans
Loop 1 dec
Input 3 retrans
Loop 1 combo
SP1 retrans
PV 2 retrans
Programmer ID num
Loop 2 inc
Disabled
Loop 2 dec
Loop 2 combo
Loop 3 inc
Loop 3 dec
Loop 3 combo
Combo example for carbon : 4 – 12 mA Air
12 – 20 mA Gas
Offset
This is the starting point, the Process Variable value at which you get 4 milliamps. Clicking on this value
will display an input box from which the user can select a new value. The range is –32768 to 32767.
Range
This is a Process Variable value between 4 and 20 milliamps. Clicking on this value will display an input box
from which the user can select a new value. The range is –32768 to 32767.
Note - The range, although not displayed with a decimal point, contains a decimal point that is dependent
on the process variable selected. For example, if the offset is 20 mV for 4 mA, and you want 100 mV to be 20
mA, then your range should be 80. If the process variable is temperature, then the range will be 80, since
temperature PVs do not have a decimal. If the PV is % Carbon, then the range will need to include the two
decimal points for % Carbon. So, a range of 80 will be entered as 8000.
See below for more examples
.