Super Systems 9130 Series User Manual
Page 104

Series 9130 Operations Manual Rev -
103
Temperature Value Column
Atmosphere Value Column
Option Value Column
Z_SETPT
Temperature Setpoint N/A
Option
This opcode is used to set the temperature set point for a zone.
The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301
(disable) – 30000.
The Option will wait for the setpoints to be reached: Blank (Don’t Wait), Wait, Wait Up, or Wait Down.
Note –
The Blank option is an actual blank line, not the word “Blank”
.
ZONE_OFF
Temperature Value
N/A
Zone
The Zone Offset opcode is used to set a temperature offset to be added to the set point sent to a specific
zone. The same loop (furnace) can have different offsets for each zone. The zones must be defined in the
zone configuration.
For example, a pit furnace has three zones: top, middle, and bottom.
The zones could be defined as:
top = zone 1
middle = zone 2
bottom = zone 3
If the
ZONE_OFF
opcode is used in a program with Temperature Value = 50 and Zone = 1 and a setpoint of
1700, then:
A set point of 1750 would be sent to the top zone (Zone 1)
A set point of 1700 would be sent to the middle zone (Zone 2)
A set point of 1700 would be sent to the bottom zone (Zone 3)
The Temperature value is the offset value to send to the specified zone. The range is -301 (disable) – 30000.
The Zone is the specific zone to send the offsets to. The options are: Zone 1 – Zone 5.