Series 9130 Operations Manual Rev -
167
9130 Analog Input Board Jumper Settings
The 9130 analog input boards are initially set up with the following configuration:
Input 1 – Temperature/Thermocouple
In order to change
these settings, the
following steps must
be taken:
1. If necessary,
shut down the
9130 screen
software by
clicking on
the
Shutdown
menu option
from the
Configuration
menu
2. Shut down
power to the
screen and
any
connected
instrument
3. Remove the cover of the 9130 instrument. This is done by removing the four (4) screws in the
corner of the 9130 instrument box, and then pushing the two (2) tabs on the side of the box outward
while pulling on the chassis
4. Remove the analog input board
5. In order for an input to be set up as a voltage input, a jumper must be placed on the two pins of the
input
6. To set an input for voltage, place the gray jumper over the two pins on the desired input. To set an
input for temperature, remove the gray jumper from the two pins on the desired input.
*** WARNING: A jumper must be placed over the input before voltage inputs can be
applied or the analog input board will be damaged ***