RAMP
Temperature Setpoint N/A
Time
This opcode changes the temperature set point linearly over time.
The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301
(disable) – 30000.
The Time is the total time for the program to reach the desired setpoint(s), in Hours:Minutes format. The
Hours range from 0 – 166, and the Minutes range from 0 – 59.
The band limit can be changed by the
SET_WAIT
opcode.
RAMPR
Temperature Setpoint Option Decimal
Rate
This opcode changes the temperature set point at a rate of degrees per minute.
The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301
(disable) – 30000.
The Option Decimal will alter the decimal point in the rate. The range is -1 (disable) – 2.
The Rate will be the rate of degrees per minute to change the temperature until the setpoint is reached.
The range is 0.01 – 300.00.
REG_INQ
Value
Register
Option
This opcode will check a specific register against a specified value and can hold until the input matches the
value.
The Value is the value to check against. The range is -301 (disable) – 32767.
The Register is the specific register to check. The range is -1 (disable) – 32767.
The options are: Equal, > Or Equal (Greater than or equal to), or < Or Equal (Less than or equal to).
RESET
Recipe Number
Recipe Step
N/A
This opcode is used to clear all stacks and timers and start a program. The RESET is useful in a weekend
shut down program to restart the normal operating program.
The Recipe Number is the program number to start once everything has been reset. The range is 1 – 300.
The Recipe Step is the step number in the program to start at. The range is 1 – 24.
RUN_SLAVE
Recipe Number
Recipe Step
Slave Instrument
This opcode will start a recipe on the specified slave SSI recipe programmer instrument.
The Recipe Number is the program number to start on the slave instrument. The range is 1 – 300.
The Recipe Step is the program step to start on in the slave instrument. The range is 1 – 24.
The Slave Instrument is the slave instrument to select to start the recipe on (SSi recipe programmers only).
The options are: 1 – 25.
SET_AUX
Setpoint Value
N/A
Slave Instrument
This opcode sends a setpoint down to an auxiliary instrument.
The Setpoint Value is the setpoint to send down. The range is -301 (disable) – 30000.
The Slave Instrument is the slave instrument to send the setpoint down to (SSi recipe programmers only).
The options are: 1 – 25.