Operating Instructions

Primetest 220

13

Attention - the protective earth conductor

current measurement can be affected by

exposure of the PrimeTest 220 to magnetic

fields or current being absorbed by the EUT

during differential leakage measurements.

Attention - where the input current waveform

displays a crest factor of 2 then a percentage

error of 2.2% is recorded on the PrimeTest 220

measured value.

8.3 Residual Current Device, RCD, Test

See figure 5

Attention - The Black 4mm test socket must not

be used whilst the PrimeTest 220 is performing

an RCD test. Electric Shock Danger!

8.3.1 Plug the supplied mains power lead into the mains

power socket 13 on the PrimeTest 220.

8.3.2 Plug the other end of the supplied mains power

lead into a mains power socket.

8.3.3 Select the RCD test function on the rotary switch

10 .

8.3.4 Switch on the mains power.

8.3.5 The PrimeTest 220 automatically checks the wiring of

the power socket being used. If the line potentials are
correct then the LCD will display the symbols PE and
PN in the steady state. Where a fault exists then the
appropriate symbol will flash (see Appendix 1) along
with the symbol being displayed in the steady state.
A fault condition will inhibit the RCD test.

If a power test is selected but the mains supply

has not been connected to the PrimeTest 220

then PE and PN symbols will flash and the test

is inhibited.