In automatic mode, the controller autonomously selects between heating
and cooling operation when the unit is first turned on. A nominal
temperature of 24 °C is preset.

AUTOMATIC MODE

Cooling MODE

COOLING OPERATION

MODE

> 6 Min.

> 3 Min.

> 6 Min.

30 sec.

30 sec.

Nominal temperature

Nominal temperature -2

°C

Fan operation IT

Fan operation AT

Compressor operation AT

Actual temperature

Start cooling mode

Cooling mode

Stop cooling mode

Functional diagram

Operation

Stop

In cooling mode, the air in the room is cooled down to the set nominal

temperature. The desired room temperature is set with the

/buttons

in 1 °C increments. If the room temperature is 1 °C above the selected

nominal temperature, the indoor unit starts to cool the air in the room.

The inverter controller checks the difference between the adjusted

nominal temperature and the actual room temperature. If there is a large

difference, the cooling output is very high. If the difference is smaller,

a lower cooling output is produced. This serves to maintain the air

discharge temperature and the room temperature.

If the adjusted room temperature is lower than approx. 2 °C, then the

control system turns the cooling function off. To protect the compressor,

the controller only turns the cooling on again after a waiting period

of 3 minutes.