REMKO ATY 261 DC User Manual
Page 9
In automatic mode, the controller autonomously selects between heating
and cooling operation when the unit is first turned on. A nominal
temperature of 24 °C is preset.
AUTOMATIC MODE
Cooling MODE
COOLING OPERATION
MODE
> 6 Min.
> 3 Min.
> 6 Min.
30 sec.
30 sec.
Nominal temperature
Nominal temperature -2
°C
Fan operation IT
Fan operation AT
Compressor operation AT
Actual temperature
Start cooling mode
Cooling mode
Stop cooling mode
Functional diagram
Operation
Stop
In cooling mode, the air in the room is cooled down to the set nominal
temperature. The desired room temperature is set with the
▲/▼buttons
in 1 °C increments. If the room temperature is 1 °C above the selected
nominal temperature, the indoor unit starts to cool the air in the room.
The inverter controller checks the difference between the adjusted
nominal temperature and the actual room temperature. If there is a large
difference, the cooling output is very high. If the difference is smaller,
a lower cooling output is produced. This serves to maintain the air
discharge temperature and the room temperature.
If the adjusted room temperature is lower than approx. 2 °C, then the
control system turns the cooling function off. To protect the compressor,
the controller only turns the cooling on again after a waiting period
of 3 minutes.
AUTOMATIC
MODE