Connection variations
of indoor unit

Unit installation

When attaching the indoor unit,
pay attention to the lower, upper
and side area air discharge.

1. Use the dimensions of the

unit to mark the fixing points
on structural parts approved
to support the static load.

2. Open the display cover(figure 8)

and remove the two screws from
underneath the filter (figure 9).

3. Remove the front of the unit

by lifting the front in the lower
area from the body approx.
10 cm and folding it upward
(figure 10)

.

4. Pull the plugs of the front cover

from the circuit board (figure 11).

5. Remove the housing's break

out opening if necessary.

6. nstall the unit on the wall.

Ensure undistorted installation.

7. Connect the refrigerant

lines, electrical cables and
condensation line to the indoor
unit as described below.

8. Check that the unit is level.

9. Re-assemble the unit.

Installation of the indoor unit

The wall bracket for the unit must
be attached with suitable screws
and anchors.

Installation

Installation may only be
performed by authorised
specialists.

NOTE

Oil return measures

If the outdoor unit is installed at
a higher level than the indoor unit,
we recommend that suitable oil
return measures are taken. Usually
an oil pump bend is installed
for every 2.5 metres of height
difference.

Oil return measures

Outdoor component

Oil pump bend

in suction pipe to

outdoor component

1 x every 2.5 metres

of rise in the line

Radius:

50 mm

max. 5 m

Outdoor component

8

Open display cover

4

Connection variations

1 Outlet on the wall, right
2 Outlet through the wall, right
3 Outlet through the wall, left
4 Outlet on the wall, left

View from the rear

1

2

9

Remove screws

10

Release unit front

11

Remove the plug

3

23