Installation inside buildings
■
Ensure that heat can dissipate
adequately when placing the
outdoor component in cellars,
attics, adjoining rooms or halls
(figure 7)
.
■
Install an additional fan with
a rated flow comparative to
that of the outdoor component
being installed in the room.
This is used in conjunction with
ventilation ducts to compensate
any pressure losses (figure 7)
■
Ensure a continuous and
unobstructed air flow from
outside, preferably using
sufficiently large air intakes
placed opposite each other
(figure 7)
.
Minimum clearances
Observe the minimum clearances
to allow access for maintenance
and repair work and facilitate
optimum air distribution.
ATY 261 DC AT
ATY 351 DC AT
A
100 mm
100 mm
B
700 mm
700 mm
C
400 mm
400 mm
D
100 mm
100 mm
E
300 mm
300 mm
■
Comply with any regulations
and conditions affecting the
structure of the building.
If necessary, fit acoustic
installation.
Minimum clearances
E
C
B
A
D
1000
1000
1000
1000
Air intake
Air
discharge
Warm air
Cold
Fresh air
Light
well
Outdoor component
Warm air
Light
well
Additional
fan
7 Installation inside buildings
300
In heating mode, condensation
formation may occur due to
cold surfaces.
NOTE
REMKO ATY
22