Remko aty, Problem display by blinker code, Off o = on × = flashes – REMKO ATY 261 DC User Manual
Page 18
Problem display by blinker code
Display
LED in AT
Fault description
Checks
Remedial measures
No.
16
red
No.
17
yellow
No.
18
green
ER01 flashes
-
-
-
Air circulation sensor on
indoor unit is defective /
triggered
Check resistance (see p. 19)
Replace defective sensor
ER02 flashes
-
-
-
Indoor unit power supply
defective
Check power supply
Repair power supply
ER03 flashes
-
-
-
Frost protection sensor on
indoor unit faulty/tripped
Check resistance (see p. 19)
Replace defective sensor
ER04 flashes
-
-
-
Vaporiser fan motor speed
too low / defective
Check fan motor, fan blade
Replace motor or blade
ER05 flashes
-
-
-
EEPROM indoor unit control
board error
ER06 flashes
-
-
-
Communication error
between IT and AT
ER07 flashes
-
-
-
Refrigerant fill quantity
incorrect
Check refrigerant pressure.
ER08 flashes
O
•
•
AT condenser sensor faulty /
tripped
Check resistance (see p. 19)
Replace defective sensor
ER09 flashes
•
O
•
Communication error
between IT and AT
Check wiring and connections
ER10 flashes
O
O
•
Compressor speed too low
Check cable connections, pipe connections,
shut-off valves, compressor
ER11 flashes
O
•
O
Over-current error
Check voltage, cable connections,
refrigerant pressure, ambient conditions
ER12 flashes
•
O
O
PFC error
Check cable connections, pipe connections,
shut-off valves, compressor
ER13 flashes
×
•
•
Inverter-control board
communication error
Check cable connections, pipe connections,
shut-off valves, compressor
ER14 flashes
•
•
×
Inverter board safety shut-off Check cable connections, pipe connections,
shut-off valves, compressor
ER15 flashes
O
•
×
Indoor unit outdoor air sensor
defective
Check resistance (see p. 19)
Replace defective sensor
ER16 flashes
×
O
•
Compressor temperature too
high
Check condenser for dirt, check refrigerant
pressure Check fan
ER18 flashes
×
O
O
EEPROM Outdoor unit
control board error
ER19 flashes
×
×
×
Compressor start error
Check cable connections, pipe connections,
shut-off valves, compressor
ER20 flashes
×
×
•
Outdoor unit system error
•
×
×
Incorrect setting type for unit Contact specialist firm
HL
O
×
•
Power supply fault
Check voltage, cable connections,
refrigerant pressure, ambient conditions
OT
×
×
O
Ambient temperature too
high
Switch unit off, switch unit back on when
ambient temperature is lower
OP
×
•
O
Liquid temperature too high
Check condenser for dirt, check refrigerant
pressure Check fan
OD
×
O
×
Hot gas temperature too high Check condenser for dirt, check refrigerant
pressure Check fan
OH
O
×
×
Inverter board overheat
• = Off
O = On
× = flashes
REMKO ATY