Before commissioning

After successful leakage test, the
vacuum pump must be connected
using the pressure gauge station
to the valve connections of
the outdoor unit (see chapter
"Leakage test") to create
a vacuum.

Perform the following checks
prior to commissioning the
unit for the first time and after

Add refrigerant

The equipment contains a
basic quantity of refrigerant.
Furthermore, for refrigerant line
lengths of more than 5 metres
per circuit, an additional amount
of refrigerant must be added,
in accordance with the following
chart:

ATY 261 DC

ATY 351 DC

Basic

line length

Additional fill quantity

Up to and

incl.

5 m

0 g/m

5 m to

max. 15 m

20 g/m

Ensure that the refrigerant in

use is always replenished in

liquid form!

NOTE

Electrical circuit diagram

any interventions affecting the
refrigerant circuit. Record the
results in the commissioning
report:

Check all refrigerant lines and
valves with leak detection spray
or soapy water for leaks and for
inadvertent mix up of suction
and injection line. Perform this
check when the unit is not
running.

Check the refrigerant lines and
insulation for damage.

Check the electrical connection
between the indoor unit and
the outdoor unit for correct
polarity.

Check that all fastenings,
mountings etc. are firm and
at the correct level.

Wear protective clothing when
handling refrigerant.

CAUTION

ATY 261 DC AT / ATY 351 DC AT

ATY 261 DC IT / ATY 351 DC IT

Display

Antifr

eeze sensor

Air cir

culation sensor

Display

Vaporiser

fan

Swing motors

Ion generator

Lift motors

Button

manual operation

Contr

ol line

Condenser

U

V

W

U

V

W

Terminal strip

Outdoor

component

Terminal strip

the indoor

unit

Contr

ol boar

d

IPM inverter power drive

IPM

Sensor

U

L in

L

L

J1

N-Out

LDC

L-Out

E

COMM

AC N In

AC N

AC L

AC L In

Condenser

J2

Test

Air-intake sensor
Condenser sensor

Hot gas sensor

L

C

J1

N out

N out

N

N

N

N

N

S

Pe

A

B

P out

P out

P

P

U

V

V

W

B

A

W

B = Condenser fan

Compr

essor

A = Reverse flow valve

J4

C

D

4
3

2

1

Mains cable

230/1Ph/50Hz

L

N

Pe

REMKO ATY

28