Remko aty, Condensate drain, Electrical connection – REMKO ATY 261 DC User Manual
Page 26
All electrical installation work
is to be performed by specialty
companies. Disconnect the
voltage supply when connecting
the electrical terminals.
CAUTION
Condensate drain
Due to the dew point shortfall
on the vaporiser, condensation is
created on the indoor unit during
the cooling operation and on the
outdoor unit during the heating
operation.
Below the vaporiser is a collection
tray, which must be connected to
a drain.
■
The condensation line is to
be installed with a minimum
slope of 2 %. (figure 11).
If necessary, fit vapour diffusion
tight insulation.
■
Lead the condensation line
freely to the run-off line. If
the condensation runs directly
into a sewer pipe, fit a trap to
prevent any unpleasant odours.
■
When operating the unit at
outdoor temperatures below
0
°C
, ensure the condensation
pipe is laid to protect it
against frost. If necessary, fit
supplementary pipe heating.
■
After completed installation,
check for unobstructed
condensation run off and
ensure that a permanent seal
is provided.
Electrical connection
Mains cable must be installed as
voltage supply to the indoor unit
and a control cable to the outdoor
component, with appropriate
safeguards.
■
We recommend installing a
main / repair switch on the
building near to the indoor unit.
■
Power is supplied to the
indoor unit, the outdoor unit
is supplied via a control line
from the indoor unit.
■
The terminal blocks for making
the connections are located
behind the cover on the
outdoor component.
■
If an optionally available
condensation pump is used
on the unit, then an additional
relay for the shut-off contact
of the pump will be needed to
increase the switching power
to shut off the compressor.
■
Control cables should be
screened if laid in areas exposed
to strong magnetic fields.
■
Electrical protection is provided
in accordance with the technical
data.
The condensation hose is designed
to be installed on the right and the
left side (view from front). Remove
the plug at the corresponding
connection.
16
Slope of the condensation line
at least
2% fall
Condensation connection - outdoor component
Opening for
Condensate drain
Condensation tray
for the outdoor unit.
Condensate drain
right or left
Indoor unit condensation connection
40
45
65
50
A condensation pump cannot
be installed within the units.
NOTE
REMKO ATY
26