Legrand SAF User Manual

Saf21/2, Raised floor box

background image

Step 1 Cut or form an 8 1/16" x 10 1/8" [205mm x

257mm] (+ 1/16" - 0") opening in the raised
floor panel and carpet. (See Fig. 1.)

Step 2 Blank communication plates come standard in floor box.

If other communication plates are required, remove
communication conduit plate. (See fig 2.) Remove only
blank communication plates that need exchanged and
attach new communication plates (sold separately) to
the floor box using (2) #8-32 x 3/8" self-tapping
screws provided. (See fig 3.) Reattach communication
compartment cover. ( See fig 2.)

FIG. 1

FIG. 3

FIG. 2

Communication

Conduit Plate

NOTE:

Communication conduit plate

required only if using conduit to supply
communications cabling. (See Step 5.)

SAF21/2

Raised Floor Box

I N S T A L L A T I O N I N S T R U C T I O N S

Installation Instruction No.: 1 002 430R3 – Updated January 2011

Legrand/Wiremold electrical systems conform to and should be properly
grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.

All electrical products may present a possible shock or fire
hazard if improperly installed or used. Legrand/Wiremold electrical
products may bear the mark of a Nationally Recognized Testing
Laboratory (NRTL) and should be installed in conformance with current
local and/or the National Electrical Code.

IMPORTANT: Please read all instructions

before beginning.

PRODUCTS COVERED:

SAF21/2

NOTE: Products are suitable for use in air handling spaces in accordance with Sec. 300-22(C) of the National Electrical Code.

CAUTION: Flange is an integral part of the box assembly. DO NOT REMOVE.

This manual is related to the following products: