MDE-4344A Series 1000 Fuel Management System Installation Manual · November 2008

Page 29

Pulser Wiring Diagrams

System and Pump/Dispenser Wiring

Pulser Wiring Notes

• All pulsers above are shown connected to hose 1.
• Jumpers on the Pump Control PCB must be properly jumpered according to the pulser

type. This should be done by the person performing the start-up. Power to the system must
not be turned on prior to this set-up.

• Refer to

“Conduit Layout”

on

page 13

for detailed system installation specifications.

• When installed in a separate DC conduit, 18 AWG wires are required for installation.

Although it is recommended that DC pulser wires be run in a conduit separate from AC
wires, they can be combined in the same conduit with AC wires providing UL-listed cable
with the following specifications is used:

Specification

Description

Conductor

18 AWG stranded wire. Number of conductors to
be determined by pulser

Shield

Foil-wrapped 100% coverage and/or tinned
copper braid 90% coverage

Drain

Wire: Stranded, tinned copper, 20 AWG or larger/
or braided shield

Voltage Rating

Maximum operating voltage of 600V

Environmental

Gas- and oil-resistant; suitable for wet or dry
locations.

Gasboy can supply Belden

®

1063A (Part Number C09655) which is a UL-listed, 4-conductor

cable that meets the requirements listed above.

Note: Belden 1063A is UL-listed but not CSA-listed.