MDE-4447A Global Pumping Unit Operation and Service Manual · May 2008

Page 23

Use Gauge Readings to Troubleshoot Self-Contained Dispensers

Troubleshooting

4

With the nozzle open, a normal vacuum reading is 6-8 inches of mercury for normal suction.
See

Figure 5-1

.

Figure 5-1: Vacuum Reading - Nozzle Open

5

With the nozzle closed, a normal vacuum reading is 0. See

Figure 5-2

.

Figure 5-2: Vacuum Reading - Nozzle Closed

Testing Pump Pressure

To test the pressure of the pump, proceed as follows:

1

Remove the pipe plug in the center of the control valve cover. Covers are marked for easy
identification.

2

Install the pressure gauge.

3

Start the pump and open the nozzle to full flow for a true reading.

4

With the nozzle open, a normal pressure reading is 16-18 PSI pressure.

5

With the nozzle closed, a normal pressure reading is 25-28 PSI pressure. See

Figure 5-3 on

page 24

.