Flowserve StarPac II Control Valves User Manual
Page 52
![background image](https://www.manualsdir.com/files/784608/content/doc052.png)
Floating
Point
Register
Attribute Description
Notes
70521
RO
Signature/Logger auxiliary 4-20 mA input
data in percent.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70523
RO
Logger setpoint data in percent.
This value is loaded from device when the
load data logger data flag is set to 1.
(Register No. 40085)
70525
RO
Logger process variable data in percent. This value is loaded from device when the
load data logger data flag is set to 1.
(Register No. 40085)
70527
RW
Calibration offset for minimum process
temperature.
Range -1.0E4 to 1.0E4. Used as
calibrated minimum temperature.
70529
RW
Positioner deviation range.
Range .1 to 100. Device will set the alarm
status bit (Positioner deviation) when the
difference between position Hallpot output
and I/P input is greater than this value.
70531
RW
Positioner change percentage over one
second.
Range .1 to 100. Device will set the alarm
status bit (Positioner deviation) when the
position percentage does not follow the I/P
percentage in one second.
70533
RW
Loss of supply air pressure ramp rate in
percent/minute.
Range 0 to 1.0E6. Rate at which the
valve will close on loss of air supply
pressure.
70535
RW
Supply pressure in psig.
Range 0 to 200.
70537
RO
Setpoint data in percent.
70539
RO
Process variable in percent.
70541
RW
Viscosity A coefficient
70543
RW
Viscosity B coefficient
70545
RO
Viscosity Correction Factor
70547
RO
Alarm state as floating point variable
70549
RW
Remote mode change register
70551 RW
Remote
command
70553
RO
Totalized liquid flow (user units)
70555
RO
Totalized gas flow (user units)
70557
RO
Cylinder top pressure (psig)
70559
RO
Cylinder bottom pressure (psig)
70561
RW
user units = 20mA at AI #2
70563
RW
user units = 4mA at AI #2
70565
RO
AI #2 (user units)
70567
RW
User flow unit multiplier
Greater than zero
70569 to
70575
N/A
Floating point expansion space.
70577
RO
Positioner Command (%)
StarPac II User Interface Manual
46