Flowserve StarPac II Control Valves User Manual
Page 50
Floating
Point
Register
Attribute Description
Notes
70459 RW
X
T
D2 curve fit coefficient.
Range -1.0E9 to 1.0E9.
70461 RW
X
T
E2 curve fit coefficient.
Range -1.0E9 to 1.0E9.
70463 RW
X
T
curve fit breakpoint.
Range 0 to 100.
70465
RW
Minimum liquid flow in selected units for
register 30018.
Range 0 to 1.0E9. Represents 0 for the
calculated integer process variable value.
70467
RW
Maximum liquid flow in selected units for
register 30018.
Range .1 to 1.0E9. Represents 9999 for
the calculated integer process variable
value.
70469
RW
Minimum gas flow in selected units for
register 30019.
Range 0 to 1.0E9. Represents 0 for the
calculated integer process variable value.
70471
RW
Maximum gas flow in selected units for
register 30019.
Range .1 to 1.0E9. Represents 9999 for
the calculated integer process variable
value.
70473
RW
Minimum upstream pressure (P1ISA) in
selected units for register 30020.
Range 0 to 1.0E9. Represents 0 for the
calculated integer process variable value.
70475
RW
Maximum upstream pressure (P1ISA) in
selected units for register 30020.
Range .1 to 1.0E9. Represents 9999 for
the calculated integer process variable
value.
70477
RW
Minimum downstream pressure (P2ISA)
in selected units for register 30021.
Range 0 to 1.0E9. Represents 0 for the
calculated integer process variable value.
70479
RW
Maximum upstream pressure (P2ISA) in
selected units for register 30021.
Range .1 to 1.0E9. Represents 9999 for
the calculated integer process variable
value.
70481
RW
Minimum delta pressure (DPISA) in
selected units for register 30022.
Range 0 to 1.0E9. Represents 0 for the
calculated integer process variable value.
70483
RW
Maximum delta pressure (DPISA) in
selected units for register 30022.
Range .1 to 1.0E9. Represents 9999 for
the calculated integer process variable
value.
70485
RW
Minimum process temperature in
selected units for register 30023.
Range -500 to 5000. Represents 0 for the
calculated integer process variable value.
70487
RW
Maximum process temperature in
selected units for register 30023.
Range -500 to 5000. Represents 9999 for
the calculated integer process variable
value.
70489
RW
Minimum auxiliary percentage for
register 30024.
Range -1.0E9 to 1.0E9. Represents 1000
for the calculated integer process variable
value.
70491
RW
Maximum auxiliary percentage for
register 30024.
Range -1.0E9 to 1.0E9. Represents 9999
for the calculated integer process variable
value.
70493
RW
Ramp rate for signature test in
percent/minute.
Range 10 to 150. Valve stem will move at
this rate during a ramp closed or ramp
open test.
StarPac II User Interface Manual
44