Flowserve StarPac II Control Valves User Manual
Page 38
![background image](https://www.manualsdir.com/files/784608/content/doc038.png)
Integer
Register
Attribute Description
Notes
40036
RW
Atmospheric pressure unit selection.
40 = psig
41 = psia
42 = kPa g
43 = kPa a
44 = kg/sq cm g
45 = kg/sq cm a
46 = bar g
47 = bar a
40037
RW
Mode source selector.
0 = Digital
1 = Discrete
2 = Remote
40038
RW
Operating mode selector.
0 = Calibration mode
1 = Manual mode
2 = Automatic mode
40039
RW
Process variable selector.
1 = Liquid flow
2 = Upstream (P
1
) pressure
3 = Downstream (P
2
) pressure
4 = Delta pressure
5 = Temperature
6 = Gas flow
7 = Auxiliary 4-20 mA input
40040
RW
Controller action selector.
0 = Reverse acting
1 = Direct acting
40041
RW
Setpoint source selector.
0 = 4-20 mA input
1 = Digital
2 = Remote
40042
RW
Air action selector.
0 = Air-to-open
1 = Air-to-close
40043
RW
4-20 mA output selector.
0 = Position
1 = Liquid flow
2 = Upstream (P
1
) pressure
3 = Downstream (P
2
) pressure
4 = Delta pressure
5 = Temperature
6 = Gas flow
7 = Auxiliary 4-20 mA input
40044
RW
Proportional band for controller.
Range 1 to 9999. Percent
40045
RW
Derivative time for controller.
Range 0 to 9999. Minutes
40046
RW
Controller integral reset.
Range 0 to 9999. Repeats/minute
StarPac II User Interface Manual
32