Flowserve StarPac II Control Valves User Manual
Page 39
![background image](https://www.manualsdir.com/files/784608/content/doc039.png)
Integer
Register
Attribute Description
Notes
40047
RW
Scaled setpoint command.
Range 0 to 9999, with fixed scale range -
12.5 to 112.5 percent.
40048
RW
Scaled digital command.
Range 0 to 9999, with fixed scale range -
12.5 to 112.5 percent.
40049
RW
Flow type indicator.
0 = Liquid
1 = Gas
40050
RW
Positioner signal source selector.
0 = Direct 4-20 mA
1 = Digital
40051
RW
Analog command signal state selector.
0 = Normal
4 mA = 0% command
20 mA = 100% command
1 = Inverted
4 mA = 100% command
20 mA = 0% command
40052
RW
Loss of analog command signal hold
time.
Range 0 to 9999. Seconds
40053
RW
Interval between data logger data points. Range 0 to 9999. Seconds
0 = Data logger inactive.
40054
RW
Actuator bottom pressure transducer
minimum calibrated ADC value
corresponding to 0 psig.
Range -32768 to 32768
40055
RW
Actuator bottom pressure transducer
maximum calibrated ADC value
corresponding to supply pressure psig.
Range -32768 to 32768
40056
RW
Actuator top pressure transducer
minimum calibrated ADC value
corresponding to 0 psig.
Range -32768 to 32768
40057
RW
Actuator top pressure transducer
maximum calibrated ADC value
corresponding to supply pressure psig.
Range -32768 to 32768
40058
RW
Minimum ADC value corresponding to
calibrated 4 mA command input.
Range 0 to 16384
40059
RW
Maximum ADC value corresponding to
calibrated 20 mA command input.
Range 0 to 16384
40060
RW
Output to I/P.
Range 0 to 65535. If system is not in
Calibration mode, writing to this register
will not have an effect.
40061
RW
Minimum DAC value corresponding to
0% position.
Range 0 to 65535.
40062
RW
Maximum DAC value corresponding to
100% position.
Range 0 to 65535.
40063
RW
Minimum ADC value corresponding to
0 °F ambient temperature.
Range -32768 to 32768
StarPac II User Interface Manual
33