Flowserve StarPac II Control Valves User Manual
Page 40
![background image](https://www.manualsdir.com/files/784608/content/doc040.png)
Integer
Register
Attribute Description
Notes
40064
RW
Maximum ADC value corresponding to
185 °F ambient temperature.
Range -32768 to 32768
40065
RW
Minimum ADC value corresponding to
4 mA on the auxiliary input channel.
Range 0 to 16384
40066
RW
Maximum ADC value corresponding to
20 mA on the auxiliary input channel.
Range 0 to 16384
40067
RW
Output from analog output channel.
Range 0 to 65535. If system is not in
Calibration mode, writing to this register
will not have an effect.
40068
RW
Minimum DAC value corresponding to
4 mA on analog output channel.
Range 0 to 65535.
40069
RW
Maximum DAC value corresponding to
20 mA on analog output channel.
Range 0 to 65535.
40070
RW
Minimum ADC value corresponding to
0 psig process pressure on upstream
pressure (P
1
) transducer.
Range -32768 to 32768
40071
RW
Maximum ADC value corresponding to
maximum psig process pressure on
upstream pressure (P
1
) transducer.
Range -32768 to 32768
40072
RW
Minimum ADC value corresponding to
0 psig process pressure on downstream
pressure (P
2
) transducer.
Range -32768 to 32768
40073
RW
Maximum ADC value corresponding to
maximum psig process pressure on
downstream pressure (P
2
) transducer.
Range -32768 to 32768
40074
RW
Minimum ADC value corresponding to
0% open from position Hallpot output.
Range -32768 to 32768
40075
RW
Maximum ADC value corresponding to
100% open from position Hallpot output.
Range -32768 to 32768
40076
RW
Minimum ADC value corresponding to
calibrated minimum temperature in °F.
Range 0 to 16384.
40077
RW
Maximum ADC value corresponding to
calibrated maximum temperature in °F.
Range 0 to 16384.
40078
RW
Totalizer reset flag.
Range 0 to 1. Writing a value of 1 to this
register causes the device to reset the
totalized flow and time.
40079
RW
Read real-time clock flag.
Range 0 to 1. Writing a value of 1 to this
register causes the device to load the real-
time clock information into real-time string.
(Register No. 50625)
40080
RW
Set real-time clock flag.
Range 0 to 1. Writing a value of 1 to this
register causes the device to set the real-
time clock from the real-time string.
(Register No. 50625)
StarPac II User Interface Manual
34