Flowserve StarPac II Control Valves User Manual
Page 43

Integer
Register
Attribute Description
Notes
40105
RW
Variable number of output No. 10 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.
30106
RO
Hardware status register.
Bit field Bit Meaning
0 Watch dog reset occurred
1 SRAM R/W failure
2 EPROM checksum error
3 NVRAM R/W failure
4 Thermocouple alarm
5 A-D converter No. 1 failure
6 A-D converter No. 2 failure
7 PII failure
8 Vcc supply failure
9 -15V supply failure
10 +.33V reference failure
11 +15V supply failure
12 D-A converter No. 1 failure
13 +10V reference failure
14 NVRAM checksum error
30107
RO
Sensor status register.
Bit field Bit Meaning
0 = P
1
sensor error
1 = P
2
sensor error
2 = Top actuator sensor error
3 = Bottom actuator sensor error
4 = Thermocouple sensor error
5 = Ambient temperature sensor error
6 = Position sensor error
40108
RW
Loss of supply pressure hold time.
Range 0 to 9999. Seconds
30109
RO
Process Variable unit type
Range 0 to 70
30110 RO
Override
status
40111
RW
Remote command refresh rate
Range 0 to 30000 sec
40112
RW
Enable mask for alarm source bit fields
Range 0 to 255, See register 30028, use
BCD
40113
RW
Pressure transducer type
0 = voltage
1 = current
40114
RW
Var number for dP valve input to be used
in flow calculation.
-1 to 1023
StarPac II User Interface Manual
37