Detailed starpac ll register map – Flowserve StarPac II Control Valves User Manual
Page 35
Detailed StarPac ll Register Map
This reference will aid you in understanding the configuration of the StarPac ll register table. Registers are
described and notes are provided that give the range and more detailed information.
The StarPac ll register table consists of three different types of information: integers, IEEE floating point
numbers and strings. These types can have a read only (RO) access attribute or a read/write (RW) access
attribute. You can only read RO registers. Writing to a RO register will generate an exception error. You
can both read and write to RW registers.
The register numbering is as follows: a 30000 base indicates RO integers, a 40000 base indicates RW
integers, a 70000 base indicates floating point numbers, and a 50000 base indicates strings. For example,
a register number of 30003 indicates a RO integer.
Two contiguous integer registers make up a floating point register. You will get an exception response if
you try to access into the middle of a floating point register.
Registers making up bit fields follow the MSB/LSB (Most Significant Byte/Least Significant Byte) format.
Internally, Valtek calculates the StarPac ll variable numbers by taking the module of the register number
and 10,000 and subtracting 1. For example, register number 30001 would become variable number 0.
Integer Registers
Integer
Register
Attribute Description
Notes
30001
RO
ADC value being output by the actuator
bottom pressure transducer.
Range -32767 to 32767.
30002
RO
ADC value being output by the actuator
top pressure transducer.
Range -32767 to 32767.
30003
RO
Indicates the input ADC value from the
external 4-20 mA command.
Range 0 to 16383.
30004
RO
Monitors the current being input to the
I/P.
Always 98.
30005
RO
Monitors the internal +10V reference
supply.
Always 547.
30006
RO
Monitors the internal +.33V reference
supply.
Always 273.
30007
RO
Monitors the internal +5V supply.
Always 3723.
30008
RO
Monitors the internal -15V supply.
Always 3366.
30009
RO
Monitors the internal +15V supply.
Always 3344.
30010
RO
ADC value being output by the ambient
temperature sensor.
Range -32767 to 32767.
30011
RO
ADC value being output by the auxiliary
4-20 mA input channel.
Range 0 to 16383.
30012
RO
ADC value being output by the upstream
process pressure (P
1
) transducer.
Range -32767 to 32767.
30013
RO
ADC value being output by the down-
stream process pressure (P
2
)
transducer.
Range -32767 to 32767.
StarPac II User Interface Manual
29