Flowserve StarPac II Control Valves User Manual
Page 51

Floating
Point
Register
Attribute Description
Notes
70495
RW
Step time value in seconds.
Range 1 to 20. Valve will move to the
stopping position immediately. The device
will collect data for the indicated amount of
time.
70497
RW
Signature starting point in percent.
Range -10 to 110.
70499
RW
Signature stopping point in percent.
Range -10 to 110.
70501
RO
Signature time data.
This value is loaded from device when the
load signature data flag is set to 1.
(Register No. 40084)
70503
RO
Signature/Logger top actuator data in
psig.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70505
RO
Signature/Logger bottom actuator data in
psig.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70507
RO
Signature/Logger I/P input data in
percent.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70509
RO
Signature/Logger position Hallpot output
data in percent.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70511
RO
Signature/Logger process temperature
data in selected units.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70513
RO
Signature/Logger upstream pressure
(P1ISA) data in selected units.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70515
RO
Signature/Logger downstream pressure
(P2ISA) data in selected units.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70517
RO
Signature/Logger liquid flow data in
selected units.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70519
RO
Signature/Logger gas flow data in
selected units.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
StarPac II User Interface Manual
45