Flowserve StarPac II Control Valves User Manual
Page 46
![background image](https://www.manualsdir.com/files/784608/content/doc046.png)
Floating
Point
Register
Attribute Description
Notes
70253
RO
Output from position Hallpot in percent.
70255
RO
4-20 mA analog auxiliary signal input
percentage.
70257
RO
Setpoint to controller in selected units.
70259
RO
Selected process variable value in
selected units.
70261
RW
Measured mechanical stroke of valve.
Range 1.0E-3 to 100
70263
RW
Softlimit maximum percentage.
Range -20 to 120. System will not open
past this percentage.
70265
RW
Softlimit minimum percentage.
Range -20 to 120. System will not close
past this percentage.
70267
RW
Full scale auxiliary input percentage.
Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.
70269
RW
Full scale delta pressure (DPISA) in
selected units.
Range .1 to 1.0E9.. Value is used to
calculate the process variable percentage.
70271
RW
Full scale liquid flow in selected units.
Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.
70273
RW
Full scale gas flow in selected units.
Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.
70275
RW
Full scale upstream pressure (P1ISA) in
selected units.
Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.
70277
RW
Full scale downstream pressure (P2ISA)
in selected units.
Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.
70279
RW
Full scale process temperature in
selected units.
Range -500 to 5000. Value is used to
calculate the process variable percentage.
70281
RW
Process temperature in selected units
equal to 0% of process.
Range -500 to 5000. Value is used to
calculate the process variable percentage.
70283
RW
Percentage of position used to output
20 mA on analog output channel.
Range .1 to 1.0E3.
70285
RW
Percentage of position used to output
4 mA on analog output channel.
Range -20 to 120.
70287
RW
Percentage of auxiliary input used to
output 20 mA on analog output channel.
Range .1 to 1.0E3.
70289
RW
Percentage of auxiliary input used to
output 4 mA on analog output channel.
Range -20 to 120.
70291
RW
Delta P (DPISA) in selected units used to
output 20 mA on analog output channel.
Range .1 to 1.0E9.
70293
RW
Delta P (DPISA) in selected units used to
output 4 mA on analog output channel.
Range 0 to 1.0E9.
70295
RW
Liquid flow in selected units used to
output 20 mA on analog output channel.
Range .1 to 1.0E9.
70297
RW
Liquid flow in selected units used to
output 4 mA on analog output channel.
Range 0 to 1.0E9.
StarPac II User Interface Manual
40