California State Fire Marshal Specifications
37.1 Bell Output Definition
The Model XR2500F panel Bell Output must be programmed to operate steady on burglary alarms and pulsed,
temporal, or California School Code on fire alarms.
New York City (MEA) Specifications
38.1 Introduction
The programming and installation specifications contained in this section must be completed when installing
the XR500 Series panel for New York City (MEA) fire alarm installations that provide a digital dialer with
network IP communication as backup. Fire alarm installations that use two digital dialer telephone lines do
not need to comply with these specifications.
38.2 Digital Dialer and Network Communication
When used with a central office communicator or a transmitter, the installation and operation of the
equipment and devices shall comply with 3RCNY 17-01. The installation shall employ the digital dialer as
the primary communicator (using telephone line) with network IP communication as backup or secondary
means of communication. It shall have the capability of transmitting separate and distinct signals to
indicate manual pull station alarm, automatic detection alarm, sprinkler waterflow alarm, supervisory signal
indications and trouble indications.
38.3 Wiring
All wiring must be in accordance with NEC, ANSI, and NFPA 70. All network cabling must be installed in
accordance with NFPA 70 for communication circuits.
38.4 Communication Programming
For digital dialer communication with supervised network backup, program the following:
PRIMARY COMM TYPE = DD
FIRST PHONE NUMBER = Central Station Receiver Phone Number
BACKUP COMM TYPE = NET
RECEIVER
ALARMS = YES
38.5 Additional Requirements
Program and install the equipment to comply with NFPA basic fire requirements. Refer to the Universal Fire
Alarm Specifications and ANSI/UL 864, NFPA 72 in this document.