beautypg.com

Accessory devices, 1 wiring diagram, 2 lightning protection – DMP Electronics XR2500F User Manual

Page 21: Installation, Power trouble alarm command

background image

XR2500F Installation Guide

Digital Monitoring Products

13

InstallatIon

Accessory Devices

10.1 Wiring Diagram

The XR2500F system below shows some of the accessory modules for use in various applications. A brief

description of each module follows.

Heat detectors, pull
stations, or any other
contact devices listed
for Fire Protective
Signaling can be
connected to zones
9 and 10.
Zones 9 and 10 and
Model 715 compatibility
identifier: A

Maximum operating
range: 9.8 VDC to
14.0 VDC.
Class B (Style A).

DMP Transformer

16 VAC 56 VA
Class 2 Wire-in.

Secondary Power Supply

1.0 Amps Max. charging
current. Use only 12 VDC
rechargeable batteries.
DMP Models 365, 366, 367,
368, or 369. Replace
batteries every 3 to 5 years.

Bell

12 VDC nominal
Minimum cutoff time is
5 minutes.
.7 Amp Max

Keypads

Model 630F
60mA at 8 to 14.5 VDC

Auxiliary Power

Total current combined from

terminals 7, 11, 25, and 27

1.9 Amp Max

Listed Resistors

1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
10K Ohm - DMP Model 308

Bell cutoff time
range is 5 to 99
minutes marchtime
and non-coded.

AC

1

2

3

4

5

6

7

8

10

11

12 13

14

15 16

17

18 19

9

20

21 22

23

24 25

26

27

28

+B

BELL GND

SMK GND

RED YEL GRN BLK

Z1

Z2

Z3

Z4

Z5

Z6

Z7

Z8 Z9+ Z9– Z10+ Z10–

AC

–B

GND

GND

GND

GND

K6

K7

Output 1

Output 2

J3

Phone Line

J10

J22
LX-Bus

Battery
Start

J23

J21

RS-232

Power
LED

J8

PROG

J4

Tamper

J16

Reset

Out1

Out2

Outputs 3-6

J11

3
4
5
6

J2

J1

Ethernet

R

L
X

Link LED

Power LED

OVC

XR2500F

Command Processor™

Panel

J6

3.3k Ohm 3.3k Ohm 3.3k Ohm 3.3k Ohm

1k Ohm

Form C Relays (J2)

Output Color Code–Model 431 Harness
Output 2 N/O Orange/White
Output 2 Com White/Gray
Output 2 N/C Violet/White
Output 1 N/O Orange
Output 1 Com Gray
Output 1 N/C Violet

Annunciator Outputs (J11)

Output Color Code
Output 3

Red

Output 4

Yellow

Output 5

Green

Output 6

Black

Front

Tamper

Rear

Tamper

s

RED

BLACK

GROUND

Cold Water
Pipe Earth
Ground

Bell

Zone

1

Zone

2

Zone

3

Zone

4

Zone

5

Zone

6

Zone

7

Zone

8

3.3k

Ohm

Resistor

3.3k

Ohm

Resistor

Zone Expander

Model 715

7mA @ 12 VDC

Models 715-8, 715-16

20mA @ 12 VDC

Smoke

Detector

Use UL Listed Power

Supervision Relay

rated at 12 VDC.

1k Ohm

s

= Supervised Circuit

Zone

9

Zone

10

22 gauge minimum

22 gauge minimum

22 gauge minimum

22 gauge minimum

RE

D

YELLOW

G

R

E

E

N

BLAC

K

1k Ohm 1k Ohm 1k Ohm

Zone Expander

Model 714

7mA @ 12 VDC

Models 714-8, 714-16

20mA @ 12 VDC

RED

YELLOW
GREEN

BLACK

RED

s

s

s

s

s

s

s s

s

s

S

S

S

S

S

S

S

S

S

S

S

S

1k

Ohm

S

S

1k

Ohm

S

S

1k

Ohm

S

S

1k

Ohm

S

S

1k

Ohm

S

S

1k

Ohm

S

S

1k

Ohm

S

S

1k

Ohm

S

S

S

S

S

S

S

S

S

S

Zone

Expander

Model 711
7mA @ 12

VDC

10k

Ohm

s

s

s

s

s

Keyswitch Arming
can be connected
to any zone. See
LT-0681.

POWER

TROUBLE

ALARM

COMMAND

1

2

3

4

5

6

7

8

9

0

ABC

DEF

GHI

JKL

MNO

PQR

STU

VWX

YX

ENABLE

SILENCE

RESET

TEST

DRILL

Fire Command Center

Verification

Zones

______

Control Unit

Delay

13.6 sec.

Smoke

Model

______

Detector

Delay

____sec.

Zones 9, 10, and all
expanded zones are
suitable for Class B (as
applicable for the
initiating and signaling
line circuits per ANSI/UL
864 Table 48.2 or 48.3).
Installation limits under
local Authority Having
Jurisdiction (AHJ).
Using verification delays
on zones 9 and 10 is
optional. Use the
delays marked on the
smoke detectors or
the smoke detector
installation wiring
diagram.

481 Z

one Expansion Interf

ace Car

d

WARNING

THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM VERIFICATION
FEATURE THAT RESULTS IN DELAY OF THE SYSTEM ALARM SIGNAL FROM
THE INDICATED CIRCUITS. THE TOTAL DELAY (CONTROL UNIT PLUS
SMOKE DETECTORS) SHALL NOT EXCEED 60 SECONDS. NO OTHER
SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ).

WARNING: Incorrect

connections may cause

damage to the unit.

CAUTION: DO NOT USE LOOPED WIRE
UNDER TERMINALS. BREAK WIRE RUN TO
PROVIDE SUPERVISION OF CONNECTIONS.

¼"

AC Wiring must be in conduit and exit
out the left side of the enclosure.

Wiring on terminals 5 through 22 must
exit right and maintain 1/4" separation
from the AC and battery positive wiring.

Figure 12: Typical XR2500F Wiring Diagram

10.2 Lightning Protection

Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on XR2500F input

and output circuits. Additional surge protection is available by installing the DMP 370 or 370RJ Lightning

Suppressors.