4 bell, 5 bell cutoff, 6 automatic bell test – DMP Electronics XR2500F User Manual
Page 41: 8 standard or encrypted line security, 9 wireless audible annunciation option, 7 standard or encrypted line security, 8 wireless audible annunciation option

XR2500F Installation Guide
Digital Monitoring Products
33
CoMPlIanCe
31.4 Bell
A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.
The alarm housing for a mercantile alarm system without a remote alarm transmission connection shall be
mounted on the outside of the building, visible from a public street or highway. It shall be accessible for
examination and repair. It shall also be located not more than four stories above the street level unless:
a) A second alarm sounding device and housing, intended for outside service, is mounted adjacent to the
premises or area of the building in which the alarm system is installed or
b) A second alarm sounding device, intended for inside service, is mounted within the premises.
In either case, the outside alarm sounding device and housing may be mounted as high as the seventh floor.
31.5 Bell Cutoff
The Bell Cutoff time cannot be less than 15 minutes.
31.6 Automatic Bell Test
The Automatic Bell Test option must be programmed as YES.
31.7 Standard or Encrypted Line Security
Standard Line Security is provided when configured as a Path 1 NET system using an XR500N panel or an
XR500 panel with an iCOM™ Network Alarm Router. The NET Check-in time must be set to 06 minutes or
RDM. When programmed for Standard Line Security, Exit Time Restart is disabled. When a dialer is required
for 06 minute check-in time, an attack resistant enclosure (DMP Model 350A) is required. When the check-in
time is set to a number less than 200 seconds, an attack resistant enclosure is not required.
To provide Encrypted Line security, install an XR500E panel or an XR500 panel with an iCOM-E™ Encrypted
Network Alarm Router.
For Encrypted Line security operation, communication between the Premise and Supervising Station provides
128 bit encryption when using an XR500E panel or an XR500 panel with an iCOM-E Encrypted Network Alarm
Router.
31.8 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as ANY for commercial applications.
31.9 Model 463G CELL Only, Standard or Encrypted Line Security
Standard or Encrypted Line Security is provided when programmed using CELL with no backup. XR500
cellular communication is used as primary with a 3 minute check-in when armed or disarmed.
Path 1 programming
Comm Type: = CELL
Checkin: = 3 minute
Path Type: = Primary
Fail Time: = 3 minute
Encrypt: = NO or YES*
Test Rpt: = NO
Sub Code: = NO or YES
*For Encrypted Line Security, program a Passphrase in Network Options.