Police Station Connected and Local Burglar Alarm Units
ANSI/UL 609
32.1 Mercantile
For Mercantile and Police Station Connect operation the Model XR500 Series must be mounted in an Attack
Resistant Housing, (DMP Model 350A or 350H).
32.2 Entry Delay
The maximum entry delay used must not be more than 60 seconds when using the Model 350A or 350H housing.
32.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
32.4 Bell
A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.
In a mercantile burglar alarm system, a mercantile alarm sounding device located within a building but outside
the protected area, is acceptable, provided it is rated for outside service and alarm conditions are transmitted to:
a) The dispatch location of the law enforcement agency having jurisdiction over the protected property or
b) A central station or residential monitoring station complying with the Standard for Central Station Alarm
Services, UL 827.
In a mercantile burglar alarm system, an alarm sounding device located within the area of greatest
protection, or outside the area of greatest protection but within an area protected by an alarm system and
that shares a common control unit with the system installed in the area of greatest protection, is acceptable
provided it is rated for inside service and alarm conditions are transmitted to:
a) The dispatch location of the law enforcement agency having jurisdiction over the protected property or
b) A central station or residential monitoring station complying with the Standard for Central Station Alarm
Services, UL 827.
An inside sounding device shall be mounted at least 10 feet (3.05 m) above the floor or at the surface of the
ceiling. When there is fixed construction within the area that could provide access for an intruder, the alarm
sounding device shall also be mounted at least 4 feet (1.2 m), as measured horizontally, away from the
edges of the fixed construction or at least 10 feet (3.05 m) above it so as to minimize access by an intruder.
32.5 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as ANY for commercial applications.
Access Control System Units
ANSI/UL 294
33.1 Panel Designation
The XR2500F is designated as a stand alone unit.
33.2 Compatible Devices
The following devices are compatible with the XR2500F panels.
Access Control
733 Wiegand Interface Module
Proximity reader connector
734 Wiegand Interface Module
Programmable proximity reader connector
OP-08CB Motion Detector
Infrared sensor.
* PB-2 REX Button
Exit control push button
PP-6005B Proxpoint Plus® Reader
Proximity reader
MP-5365 Miniprox® Reader
Slimline proximity reader
PR-5455 ProxPro® II Reader
Long range reader with sounder
MX-5375 Maxi-Prox™ Reader
Long range reader compatible with 1351 Prox Pass
* This device has not been investigated and shall not be used in listed installations.