Smoke and glassbreak detector output, 1 terminals 11 and 12, 2 current rating – DMP Electronics XR2500F User Manual
Page 29: Powered zones for 2-wire smoke detectors, 1 terminals 25–26 and 27–28

XR2500F Installation Guide
Digital Monitoring Products
21
InstallatIon
Smoke and Glassbreak Detector Output
14.1 Terminals 11 and 12
Terminal 11 supplies positive 12 VDC regulated to power 4-wire smoke detectors and other powered devices.
This output can be turned off by the user for five seconds using the Sensor Reset User Menu option to allow
latched devices to reset. Terminal 12 is the ground reference for terminal 11.
14.2 Current Rating
The	Output	current	from	terminal	11	is	shared	with	terminals	7,	25,	and	27.	
The	total	current	draw	of	all	devices	powered	from	the	panel	must	be	included	with	terminal	11	calculations	
and must not exceed the maximum output rating.
Powered Zones for 2-Wire Smoke Detectors
15.1 Terminals 25–26 and 27–28
Panel terminals 25 through 28 provide two resettable Class B, Style A, 2-wire powered zones. For
programming	purposes	the	zone	numbers	are	9	and	10.		
Note:		The	maximum	wire	length	for	either	zone	9	or	zone	10	is	3000	feet	using	18	AWG	or	1000	feet	using	
22 AWG. The maximum voltage is 14 VDC and the maximum normal standby current is 1.25mA DC. The
maximum	line	impedance	is	100	Ohms.		The	maximum	short	circuit	current	is	56mA.
When	using	725	Zone	Expansion	Modules,	use	included,	listed	6.8k	Ohm	EOL	resistors.		The	compatibility	
identifier for the zones using 725 Zone Expansion Modules is B. When using 715 Zone Expansion modules,
use listed 3.3k Ohm EOL resistors, Model 309. For all other zone expansion modules, use listed 1.0k Ohm
Model	310	EOL	resistors.		The	compatibility	identifier	for	the	zones	is	A.		
Note:	Do	not	mix	detectors	from	different	manufacturers	on	the	same	zone.
Caution:	Performing	a	Sensor	Reset	momentarily	drops	power	to	the	devices	on	Zones	9	and	10.		The	panel	
views these zones (9 and 10) as “Open” while the power is absent.
