8 standby battery selection – DMP Electronics XR2500F User Manual
Page 27

XR2500F Installation Guide
Digital Monitoring Products
19
InstallatIon
11.8 Standby Battery Selection
To choose the type and number of batteries needed for 24, 60, or 72 hours of standby power based on the
Amp	Hours	Required	calculation	from	the	XR2500F	Power	Requirements	section,	perform	the	following:
1.	Select	the	desired	standby	hours	required	from	the	table	below:	24,	60,	or	72	hours
2.	Select	the	desired	battery	size:	Model	368	(12	VDC	4.5	Ah),	Model	369	(12	VDC	7	Ah),	 
Model 367 (12 VDC 7.7 Ah), Model 365 (12 VDC 9 Ah), Model 366 (12 VDC 18 Ah).
3. Select a Max. Ah Available number that is just greater than the number calculated as the Amp Hours
Required.
4.	Install	the	number	of	batteries	shown	in	the	corresponding	No.	of	Batteries	required	column.
Example:	 If	the	Amp	Hours	Required	calculation	equals	22	Ah	for	24	hours	of	standby	time	and	4.5	Ah	 
batteries are desired, install six (6) Model 368 (12 VDC, 4.5 Ah) batteries.
For listed installations, all batteries shall be installed in a DMP Model 341, 349, 350, or 352S enclosure
and all wiring shall run through conduit. The enclosure shall be installed to the left of the XR2500F
enclosure to ensure Battery and AC wire separation.
24 hours of standby power
4.5 Ah Batteries
7 Ah Batteries
7.7 Ah Batteries
9 Ah Batteries
18 Ah Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
8
2
6
1
6
1
8
1
16
1
12
3
12
2
13
2
16
2
32
2
16
4
18
3
20
3
24
3
48
3
20
5
24
4
27
4
32
4
24
6
31
5
34
5
40
5
28
7
37
6
41
6
32
8
43
7
36
9
Note: 48 hours is the typical battery recharge time for any of the Number of
Batteries shown in this section.
40
10
60 hours of standby power
7 Ah Batteries
7.7 Ah Batteries
9 Ah Batteries
18 Ah Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
13
2
14
2
17
2
17
1
20
3
22
3
26
3
34
2
27
4
29
4
34
4
52
3
33
5
37
5
43
5
69
4
40
6
44
6
52
6
47
7
52
7
61
7
Note: 48 hours is the typical battery
recharge time for any of the Number
of Batteries shown in this section.
54
8
59
8
69
8
60
9
67
9
67
10
72 hours of standby power
9 Ah Batteries
18 Ah Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
16
2
16
1
25
3
33
2
33
4
50
3
42
5
67
4
50
6
59
7
Note: 72 hours is the typical battery recharge time required for any of the Number
of Batteries shown in this section.
67
8
Note: If the Amp Hours Required calculation is greater than any Max. Ah Available number shown on a table, then
add power supply(s) to power some system devices allowing the Amp Hours Required calculation to be reduced. See
the 710/710F Bus Splitter/Repeater Installation Guide (LT-0310).