IntRoduCtIon

Expansion

9.1 Zone Expansion

Up to 574 fire and burglary zones are available on the XR2500F using DMP Security Command keypad remote

zone capability and zone expansion modules. The panel keypad data bus supports up to sixteen supervised

device addresses with each address supporting up to four programmable expansion zones.
Up to 500 zones are available using the on-board LX-Bus along with additional expansion modules. Use the

461 Interface Adaptor, 462N, 462P, 463G, or 481 interface cards, and any combination of sixteen, eight, four,

and single point zone expander modules and single point LX-Bus detectors.
Combined current requirements of additional modules may require an additional power supply. See the

710/710F Bus Splitter/Repeater Installation Guide (LT-0310). Refer to the Standby Battery Calculations

section when calculating power requirements.
Note: Do not use shielded wire for LX-Bus or Keypad Bus circuits.

9.2 Output Expansion

Note: Do not use shielded wire for LX-Bus or Keypad Bus circuits.
In addition to the two SPDT relays and four programmable open collector outputs on the XR2500F, you can

also connect up to 25 programmable Model 716 Output Expansion Modules to each LX-Bus. These modules

can provide an additional 500 programmable SPDT relays.
The XR2500F provides 100 Output Schedules you can use for programming the 716 to perform a variety of

annunciation and control functions. You can also assign the 716 outputs to any panel Output Options such as

Fire Alarm, Communication Fail, or Phone Trouble Outputs. Refer to the 716 Installation Guide (LT-0183).
The LX-Bus™ also supports the Model 717 Graphic Annunciator Module. Each 717 module supplies 20

switched ground outputs that follow the state of their assigned zones.
Note: The 717 supports the first eight keypad bus zones. To follow Keypad Bus zones nine through 16, install

multiple 716 modules. Refer to the 717 Installation Guide (LT-0235) and 716 Installation Guide (LT-0183).