Installation – DMP Electronics XR2500F User Manual
Page 26
![background image](/manuals/76079/26/background.png)
Digital Monitoring Products
XR2500F Installation Guide
18
InstallatIon
Standby Battery Power Calculations
Standby Current
Alarm Current
736P POPIT Interface Module
Radionics Popex, POPITs, OctoPOPITs
Qty ______
Qty ______
x
x
25mA
___mA
______
______
Qty ______
Qty ______
x
x
25mA
___mA
______
______
710 Bus Splitter/Repeater Module
Qty ______
x
32mA ______
Qty ______
x
32mA ______
710F Fire Bus Splitter/Repeater Module
Qty ______
x
40mA ______
Qty ______
x
40mA ______
711 Zone Expansion Module
Active Zones (EOL Installed)
Qty ______
Qty ______
x
x
11mA
1.6mA
______
______
Qty ______
Qty ______
x
x
11mA
*2mA
______
______
714 Zone Expansion Module
Active Zones (EOL Installed)
Qty ______
Qty ______
x
x
7mA
1.6mA
______
______
Qty ______
Qty ______
x
x
7mA
*2mA
______
______
714-8, 714-16 Zone Expansion Module
Active Zones (EOL Installed)
Qty ______
Qty ______
x
x
20mA
1.6mA
______
______
Qty ______
Qty ______
x
x
20mA
*2mA
______
______
715 Zone Expansion Module
Active Zones (EOL Installed)
2-Wire Smokes
Qty ______
Qty ______
Qty ______
x
x
x
7mA
4mA
.1mA
______
______
______
Qty ______
Qty ______
Qty ______
x
x
x
7mA
*30mA
.1mA
______
______
______
715-8, 715-16 Zone Expansion Modules
Active Zones (EOL Installed)
2-Wire Smokes
Qty ______
Qty ______
Qty ______
x
x
x
20mA
4mA
.1mA
______
______
______
Qty ______
Qty ______
Qty ______
x
x
x
20mA
*30mA
.1mA
______
______
______
716 Output Expansion Module
Active Form C Relays
Qty ______
x
13mA ______
Qty ______
Qty ______
x
x
13mA
12mA
______
______
717 Graphic Annunciator Module
Annunciator Outputs
Qty ______
x
10mA ______
Qty ______
Qty ______
x
x
10mA
1mA
______
______
521LX, 521LXT Smoke Detectors
Qty ______
x
8.8mA ______
Qty ______
x
*28mA ______
Aux. Powered Devices on Terminals 7 and 11
Other than Keypads and LX-Bus Modules
______mA
______mA
This page only
Sub-Total Standby ______mA
Sub-Total Alarm ______mA
Sub-Totals from previous page
Sub-Total Standby ______mA
Sub-Total Alarm ______mA
*Based on 10% of active zones in alarm
Total Standby ______mA
Total Alarm ______mA
Total Standby______mA x number of Standby Hours needed
Total Alarm
______ =
______mA
Total
_______mA-hours
+_______mA-hours
_______mA-hours
X .001
= _______Amp-hrs
Required