XR2500F Installation Guide

Digital Monitoring Products

37

CoMPlIanCe

Control Units for Fire-Protective Signaling Systems

ANSI/UL 864, NFPA 72

35.1 Power Supply

For listed installations, the total current combined from Auxiliary and Bell Power cannot exceed:

1.2 Amps with a 56 VA transformer; .5 Amp Max for Auxiliary Power and .7 Amp Max for Bell

Combined total current from Terminals 7, 11, 25, and 27 cannot exceed 1.2 Amps.

35.2 Zone Restoral Reports

The Restoral Reports option must be selected as YES or Disarm. .

35.3 Power Fail Delay

The Power Fail Delay option must be selected as required by the service of the panel. For Central Station or

Remote Station service: 1.

35.4 Sprinkler Supervisory

Any zone used for sprinkler supervisory must be programmed with “SPRINKLR XXX” as the zone name. The

last three characters in the zone name may be assigned a number to identify the zone. The Model 893A Dual

Phone Line Module must be used on all sprinkler supervisory systems.

35.5 DACT Systems

Two phone lines must be used. The two phone lines cannot be ground start or party lines. The 893A Dual

Phone Line Module is used to provide two phone line connections to the system. The 2ND Phone Line

communication option must be selected as DD.
Two different phone numbers must be programmed for digital communication. The Test Time option must be

programmed so that the XR2500F sends a report every 24 hours.

35.7 Local Protective Signaling Systems

The DMP Model 865, 866, or 867 Notification Circuit Module must be used on the bell circuit for detection of

shorts and grounds. See this guide for wiring diagrams. Any burglary or other off premises communication

must be done with the Model 893A Dual Phone Line Module. For local commercial fire installations, the 893A

is required.

35.8 Remote Station Protective Signaling Systems

You must provide 60 hours of standby battery. See this guide for standby battery calculations. Two

Radionics Model D127 Reversing Relay Modules provide two reversing polarity telephone connections. See

the D127 Installation Instruction sheet for wiring details. A DMP Model 893A is used to provide two line dialer

communication.

35.9 Fire Protective Signaling Systems using Internet/Intranet Networks

The XR2500F panel must be programmed as described below for Fire Protective Signaling Systems using NET

Communication Type.
• SUB CODE must be programmed as YES

• FAIL TIME must be programmed as 5

• CHECKIN must be programmed as 3

• SEND COMM TRBL must be programmed as YES

35.10 Combination Systems

For combination fire and burglary systems, powered burglary devices (PIR, Glassbreak, etc.) must be

powered from a separate listed power supply (DMP Model 505-12). This requirement is not needed for non-

powered burglary devices (door contacts, etc.) which only connect to the zone input of zone expanders or

keypads. Refer to Powered Burglary Devices in this document.
For combination fire and burglary systems, burglary sounding devices such as sirens and bells must be

energized using panel relays, 860 relays, or 716 relays. Programming the output to activate the relay must

occur using the Burglary Bell Output option in Area Information or by the Alarm Action output option of Zone

Information. The Burglary Bell Action option of the panel Bell Options must be programmed as None.

35.11 Remote Annunciators

At least one Model 630F Remote Annunciator must be used on the system. All fire alarms, fire troubles and

supervisory alarms or troubles must be annunciated only on the 630F. All burglary alarms or troubles must

only be annunciated on non-fire keypads. See Status List options of the XR500 Series Programming Guide

(LT-0679).