J22 lx-bus expansion connector, 1 description, 2 lx-bus interface cards – DMP Electronics XR2500F User Manual
Page 34: 3 lx-bus leds, Ovc led, J21 serial connector, 2 serial connector leds
![background image](/manuals/76079/34/background.png)
Digital Monitoring Products
XR2500F Installation Guide
26
InstallatIon
J22 LX-Bus Expansion Connector
20.1 Description
J22 LX-Bus and J21 RS-232 connectors cannot be used at the same time. Either use J21 to connect a serial
device for PC Log Reporting, or use J22 to connect an LX-Bus or Wireless device. This is determined by
where you install the jumper on J23 6-Pin Header. Reset the panel using J16 jumper to activate selected J23
operation. See the Connecting LX-Bus and Keypad Bus Devices section for maximum wiring distances.
Note: Do NOT use shielded wire when using the LX-Bus. Do NOT connect the wires from the 4-wire harness
to the panel terminals.
20.2 LX-Bus Interface Cards
Refer to the following tables to identify zone locations and numbers relative to J22 operation.
J22 LX-Bus Enabled
AND
One Interface Card
OR
461 Adaptor Card and
Multiple Interface
Cards
LX-Bus Zone Numbers
LX-Bus Zone Numbers
LX-Bus Zone Numbers
1
500-599
2
600-699
2 (A)
600-699
3 (B)
700-799
4 (C)
800-899
5 (D)
900-999
J22
LX-Bus
NOT
Enabled
One Interface Card
OR
461 Adaptor Card and
Multiple Interface
Cards
LX-Bus Zone Numbers
LX-Bus Zone Numbers
1
500-599
1 (A)
500-599
2 (B)
600-699
3 (C)
700-799
4 (D)
800-899
5 (E)
900-999
20.3 LX-Bus LEDs
The two LEDs, located near the bottom-right corner of J21 indicate data transmission and receipt. The
top LED flashes green to indicate the panel is transmitting LX-Bus data. The bottom LED flashes yellow to
indicate the panel is receiving LX-Bus data.
20.4. OVC LED
The Overcurrent LED (OVC) lights Red when the devices connected to the Keypad Bus and LX-Bus(es) draw
more current than the panel is rated for. The OVC is located above Outputs 1 and 2 on the panel and turns a
steady Red when lit. When the OVC LED lights Red, the LX-Bus(es) and keypad bus shut down.
J21 Serial Connector
21.1 Description
Note: J22 LX-Bus and J21 RS-232 connectors cannot be used at the same time. Either use J21 to connect a
serial device, or use J22 to connect an LX-Bus or Wireless device. This is determined by where you install
the jumper on the J23 6-Pin Header. Reset the panel using J16 jumper to activate selected J23 operation.
The maximum line impedance is 100 Ohms.
To enable J21 to operate in RS-232 mode place a jumper on the two pins next to the letter “R” on the J23
6-Pin header. The Serial Connector allows the XR2500F panel to transmit PC Log Reports directly to an
RS-232 device.
21.2 Serial Connector LEDs
The two LEDs, located near the bottom-right corner of J21 indicate data transmission and receipt. The
top LED flashes green to indicate the panel is transmitting serial data. The bottom LED flashes yellow to
indicate the panel is receiving serial data.