beautypg.com

5 troubleshooting, 1 general, 2 led indications – Bronkhorst EL-FLOW Base 2014 User Manual

Page 31: 3 troubleshooting summary general, Hc , h c

background image

BRONKHORST HIGH-TECH

5 Troubleshooting

5.1

General

For a correct analysis of the proper operation of a flow/pressure meter or controller it is recommended

to remove the unit from the process line and check it without applying fluid supply pressure. In case the

unit is dirty, this can be ascertained immediately by loosening the compression type couplings and, if

applicable the flange on the inlet side.

Energizing or de-energizing of the instrument of the instrument indicates whether there is an electronic

failure.

After that, fluid pressure is to be applied in order to check behaviour.

If there should be suspicion of leakage in case of a gas unit, do not check for bubbles with a leak

detection liquid under the cover as this may lead to a short-circuit in the sensor or p.c.board.

5.2

LED indications

The two LEDs on the instrument give information about the status of the instrument. Check chapter 3.6,

“LED indications” for detailed info.

5.3

Troubleshooting summary general

Symptom

Possible cause

Action

No output signal

No power supply

1a) check power supply

1b) check cable connection

Output stage blown-up due to long lasting

shortage and/or high-voltage peaks

1c) return to factory

Supply pressure too high, or differential

pressure across meter too high

1d) lower supply pressure

Valve blocked/contaminated

1e) connect 0 .. 15 Vdc to valve and

slowly increase voltage while supply

pressure is ‘on’. The valve should open at

7V ± 3V; if not open, then cleaning parts

and adjust valve (qualified personnel

only)

Screen in inlet fitting blocked

1f) clean screen

Sensor/capillary failure

1g) return to factory

Maximum output signal

Output stage blown-up

2a) return to factory

Sensor/capillary failure

2b) return to factory

Output signal much lower than

setpoint signal or desired flow

Screen blocked/contaminated

3a) clean screen

LFD blocked/contaminated and/or liquid in

meter

3b) remove LFD and clean; dry meter
with air or

2

N

Valve blocked/contaminated

3c) clean valve

Valve internal damage (swollen seat in

plunger)

3d) replace plunger assembly and adjust

valve or return

Incorrect type of gas is used and/or

pressure/diff. pressure

3e) try instrument on conditions for

which it was designed

Flow is gradually decreasing

Condensation, occurs with

3

NH

,

hydrocarbons such as

10

4

8

3

H

C

,

H

C

etc.

4a) decrease supply pressure and/or heat

gas to be measured

Valve adjustment has changed

4b) see ‘1e’

Oscillation

Supply pressure/diff. pressure too high

5a) lower pressure

Pipeline too short between pressure regulator

and MFC

5b) increase length or diameter of piping

upstream

Pressure regulator is oscillating

5c) replace pressure regulator or try ‘5b’

Valve sleeve or internals damaged

5d) replace damaged parts and adjust

valve, see ‘1e’ or return to factory

Controller adjustment wrong

5e) adjust controller

9.17.061

EL-FLOW Base Series Mass Flow Controllers

Page 31