beautypg.com

1 slave address, baud rate and parity setup – Bronkhorst EL-FLOW Base 2014 User Manual

Page 16

background image

BRONKHORST HIGH-TECH

Physical layer and communication protocol are detected automatically upon reception of messages.

These messages must be sent using the correct combination of physical layer and communication

protocol. After every power-up the communication detection mode is active.

3.4.1 Slave address, baud rate and parity setup

Default instruments will be delivered to customers on address 1 and with a baud rate of 19200 baud and

EVEN parity.

The slave address, baud rate and parity of the Bronkhorst meter/controller Modbus slave can be

changed to fit the instrument in your existing Modbus network. Changing the slave address, baud rate

and parity can be done in the following ways.

Using RS232: FlowDDE

‘Off-line’ via the RS232 communication port by means of FlowDDE. This program can be used to

read/change parameters, including the slave address, baud rate and parity.

Connect your Bronkhorst meter/controller Modbus slave instrument to a free COM-port using the

special cable with on one side a T-part with male and female sub-D 9 connector and on the other side a

female sub-D 9 connector (part number 7.03.366). The single sub-D 9 connector should be connected to

your COM-port and the female sub-D 9 of the T-part to the male sub-D 9 of the instrument. Standard

cables are approx. 3 meters. Maximum length between PC and instrument allowed is approximately 10

meters.

Start FlowDDE and open communication via the menu (as shown below) or by pressing .

Once the DDE server is active, open the FlowDDE Test Form via the menu (as shown below) or by

pressing .

Page 16

EL-FLOW Base Series Mass Flow Controllers

9.17.061