Installation

(for qualified installers only)

2 7

Travis Industries

4 0 2 0 8 1 2

9 3 5 0 8 1 1 0

Horizontal Terminations with 3 Vertical Elbows (Top Vent Configuration)

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.

NOTE:

• A total of three elbows must be used.

• No horizontal elbows may be used (a horizontal elbow is

defined as an elbow that directs the vent from a horizontal

direction to another horizontal direction).

• Two 45° elbows may be substituted for two of the 90° elbows.

• Horizontal sections require a 1/4" rise every 12" of travel.

• The maximum vertical height is 19'.

• The maximum horizontal length is 20'.

Horizontal Elbows are

NOT ALLOWED

5 feet

0 feet

0 feet

5 feet

0 feet

19' (max)

19' (max)

5 feet

10 feet

5 feet

10 feet

0 feet

15 feet

20' (max)

10 feet

15 feet

15 feet

20' (max)

10 feet

15 feet

Restrictor

Position #1

Min. 24" Rise

Before First Elbow