Installation, Four 45° offsets, Zero or two 45° offsets – Avalon Firestyles DVL Fireplace-1999 to 2002 User Manual

Page 27: For qualified installers only), Travis industries

background image

Installation

(for qualified installers only)

2 5

Travis Industries

4 0 2 0 8 1 2

9 3 5 0 8 1 1 0

Vertical Terminations with 0, 2, or 4 45° Offsets (Top Vent Configuration)

Use 8” diameter co-axial vent

A Maximum of Four 45° Elbows May be Used

8’ Minimum System Height (without offsets)

40 Maximum System Height

12’ Maximum Horizontal Offset (6’ 6” for 4 Offsets)

Offset Length

Hor. Offset

Vert. Rise

None

5"

1'

1' Section

1'

1' 7"

2' Section

1' 9"

2' 4"

3' Section

2' 5"

3'

4' Section

3' 2"

3' 8"

Offset
Length

Horizontal
Offset

Vertical

Rise

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.

5 feet

10 feet

(min.)

15 feet

20 feet

25 feet

30 feet

0 feet

35 feet

0 feet

5 feet

6' 6"

(max)

5 feet

0 feet

0 feet

5 feet

6' 6"

(max)

10 feet
(min.)

15 feet

20 feet

25 feet

30 feet

35 feet

Four 45° Offsets

5 feet

10 feet

15 feet

20 feet

25 feet

30 feet

0 feet

40' (max)

0 feet

5 feet

5 feet

0 feet

0 feet

10 feet

15 feet

20 feet

30 feet

Zero or Two 45° Offsets

5 feet

12'

(max)

25 feet

10 feet

12'

(max)

10 feet

Restrictor

Position # 1

35 feet

35 feet

40' (max)

40' (max)

40' (max)

Restrictor

Position # 1