Installation, Clearances (top vent configuration), Straight lengths – Avalon Firestyles DVL Fireplace-1999 to 2002 User Manual
Page 24: Firestops & support, Terminations, Elbows
2 2
Installation
(for qualified installers only)
Travis Industries
4 0 2 0 8 1 2
9 3 5 0 8 1 1 0
Altitude Considerations (Top Vent Configuration)
This heater has been tested at altitudes ranging from sea level to 8,000 feet (2,400 M). In this testing we have
found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
!
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.
Clearances (Top Vent Configuration)
Horizontal Runs
Vertical Sections
Min. 3" Clearance
Above 45° Sloping Vent
Min. 2" Clearance to
the Sides of the Vent
The DVL FP Top-Vent Firestop is
required (part # 93006096) when
passing through any wall.
Min. 3" Clearance
Above the Vent
Min. 2" Clearance
to the Sides
Min. 75"
(from base of fireplace)
Min. 24" rise
before first elbow.
Min. 84-1/2"
(from base of
fireplace)
The DVL FP Top-Vent
Firestop is required (part #
93006096) whenever
passing through a ceiling
(or enclosure) and at every
floor penetration.
Min. 1" Clearance
Below the Vent
Min. 1" Clearance
Below the Vent
Approved Vent Components for Top Vent Configuration
•
Use 8” diameter Model GS Direct Vent manufactured by Simpson Dura-Vent
only
. Follow the
installation instructions included with the vent. For the nearest Simpson Dura-Vent supplier, call (800)
835-4429. Vent part numbers and descriptions are listed below.
Straight Lengths
1208B
6" Pipe Length, Black
1207B
9" Pipe Length, Black
1206B
12" Pipe Length, Black
1204B
24" Pipe Length, Black
1203B
36" Pipe Length, Black
1202B
48" Pipe Length, Black
1211B
11” to 14-5/8" Adjustable, Black
Firestops & Support
93006096
DVL FP Top-Vent Firestop (Horizontal or Vertical)
1288
Wall Strap
Terminations
1284
Horizontal Square Termination
1285
Hor. High Wind Termination
1250
Vinyl Siding Stand-off
1291
Travis Vertical Termination
Elbows
1245B
45° Elbow, Black
1290B
90° Elbow, Black