For qualified installers only!

Insert Placement (continued)

¥

Insert must be placed so no combustibles are within, or can swing within 36" of the front of the
heater (e.g. drapes, doors)

¥

The insert may be placed inside a masonry fireplace or listed zero-clearance (metal) fireplace

¥

The insert must be installed in a level, undamaged fireplace (damage must be repaired prior to
installation)

¥

The insert must maintain 10" clearance to sidewalls (measure to the upper top, 22-1/4" from center)

¥

Non-combustible facing (e.g. brick, tile) must extend 8" minimum from the side and to the top of the
insert (measure to the upper top, 40-1/2" wide by 28-3/8" high)

¥

Combustible mantles must be a minimum 17-1/2" above the top of the insert (measure to the upper
top, 37-7/8" above the hearth)

+

Clearances may be reduced by methods specified in NFPA 211, listed wall shields or other means
approved by local building or fire officials.

Floor Protection

¥

The heater must be installed on a non-combustible hearth and may not extend over combustible
flooring

Gas Line Install

!

The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI Z223.1
and the requirements listed below.

!

The heater and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig,
isolate the gas supply piping by closing the manual shutoff valve.

¥

The gas line must be properly purged to release all air in the gas line prior to starting the heater.

¥

Leak test all gas line joints and the gas control valve prior to and after starting the heater.

Gas Line Connection

¥

The gas inlet accepts a 3/8" F.P.T. Fitting

¥

The location of the gas inlet is shown below

¥

A manual shutoff valve is required for installation (it must be located within 3' of the heater)

NOTE:
With the insert in
place, the gas line
center is located 4-
5/8" back from the
fireplace opening,
1-1/2" above the
hearth, and 10-
3/8" from the
center of the
insert.