For qualified installers only!
Gas Line Install
!
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI Z223.1
and the requirements listed below.
!
The heater and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig,
isolate the gas supply piping by closing the manual shutoff valve.
¥
The gas line must be properly purged to release all air in the gas line prior to starting the heater.
¥
Leak test all gas line joints and the gas control valve prior to and after starting the heater.
Fuel
¥
This heater is designed either for natural gas or for propane (but not for both). Check the sticker on
the top of the gas control valve to make sure the correct fuel is used.
Gas Line Connection
¥
The gas inlet accepts a 3/8" F.P.T. Fitting
¥
The location of the gas inlet is shown below
12-5/8"
2-5/8"
1-1/2"
¥
A manual shutoff valve is required for installation (it must be located within 3' of the heater)